COMPACT WALL AXIAL FANS - Air and Sound
Performance Data.
LICENSED PERFORMANCE. Cfm @ inches WG. (4 Pole Single Phase Motors)
| MODEL |
Input Watts |
Peak BMP |
rpm |
0 |
0.05 |
0.1 |
0.15 |
0.2 |
0.25 |
0.3 |
0.35 |
0.4 |
0.5 |
Sones |
| HCGB/4-12/G-A |
132 |
- |
1500 |
1260 |
1200 |
1130 |
1040 |
900 |
- |
- |
- |
- |
- |
9.9 |
| HCGB/4-16/G-A |
310 |
0.26 |
1500 |
2430 |
2350 |
2260 |
2160 |
2050 |
1840 |
1500 |
- |
- |
- |
18.9 |
| HCGB/4-18/G-A |
550 |
0.5 |
1465 |
3690 |
3600 |
3510 |
3410 |
3330 |
3240 |
3140 |
3020 |
2900 |
2500 |
19.7 |
| HCGB/4-20/G-A |
750 |
0.65 |
1500 |
4520 |
4440 |
4340 |
4220 |
4100 |
3990 |
3870 |
3740 |
3600 |
3160 |
28 |
Performance is shown for Soler & Paiau COMPACT WALL AXIAL FANS.
Speed (rpm) shown is nominal. Performance is based on actual speed
of the test. Performance ratings include the effects of finger guards
in the airstream. Performance shown is for installation type A:
Free inlet, Free outlet. The sound ratings are loudness values in
fan sones at 5ft (1.5m| in a hemispherical free field calculated
per AMCA Standard 301. Values are shown are for installation type
A: free inlet fan sone levels.
COMPACT DUCT AXIAL FANS - Air and Sound
Performance Data.
LICENSED PERFORMANCE. Cfm © inches WG. (4 Pole Single Phase
Motors)
| MODEL |
Input Watts |
Peak BHP |
rpm |
0 |
0.05 |
0.1 |
0.15 |
0.2 |
0.25 |
0.3 |
0.35 |
0.4 |
0.5 |
Sones |
| TCGB/4-12/G-B |
132 |
- |
1500 |
1216 |
1130 |
940 |
570 |
- |
- |
- |
- |
- |
- |
11.6 |
| TCGB/4-16/G-B |
320 |
0.28 |
1500 |
2540 |
2440 |
2330 |
2200 |
2030 |
1760 |
- |
- |
- |
- |
17.6 |
| TCGB/4-18/G-B |
540 |
0.48 |
1465 |
3620 |
3510 |
3370 |
3260 |
3140 |
3000 |
2800 |
- |
- |
- |
24 |
| TCGB/4-20/G-B |
770 |
0.67 |
1500 |
4750 |
4630 |
4500 |
4380 |
4240 |
3090 |
3930 |
3660 |
- |
- |
32 |
Performance is shown for Soler & Palau COMPACT DUCT AXIAL FANS.
Speed {rpm) shown is nominal. Performance is based on actual speed
of the test. Performance ratings do not include the effects of appurtenances
in the airstream. Performance shown is for installation type A:
Free inlet, Free outlet. The sound ratings are loudness values in
fan sones at 5ft (1.5m) in a hemispherical free field calculated
per AMCA Standard 301. Values are shown are for installation type
A: free inlet fan sone levels.
|